Insulation Properties :

Closed cell expanded polyethylene
Heat conduction at 24°C 0,0383 W/m°K
Working temperature: from - 45°C to 105°C
Reaction to fire: self-extinguishing DIN 4102-B1 (P-BWU03-I-16.5.312) and
EURO CLASS B-s2,d0
Vapour resistance: µ > 5000
Average density of the insulation: 35 ± 5 Kg/m3
White external extruded PE-layer, non-toxic and resistant to external chemical agents
and ultra-violet rays.
ISO 9002 EN 29002 Certificates

 

Pipe Properties :
APPLICATIONS

Ottocool receiver tubes HVACR industry or compressive strength, flexibility, thermal conductivity, such as weight per meter features a special production for OEM applications that require customized sizes or standard sizes are available.

Ottocool alc standard copper pipe can be processed in the same manner and with the same tools. (E.g., cutting, expansion, bending, etc.)

 

Ottocool AlCu

Pipes

Max. Operating Pressure

       Max. Compressive         strength

Expansion

1/4 "x 0.80mm

55 Bar (800psi)

> 3,5 x Max Operating Pressure

>% 40

3/8 "x 0.80mm

55 Bar (800psi)

> 3,5 x Max Operating Pressure

>% 40

1/2 "x 1.00mm

55 Bar (800psi)

> 3,5 x Max Operating Pressure

>% 40

5/8 "x 1,20 mm

55 Bar (800psi)

> 3,2 x Max Operating Pressure

>% 40

 

ADVANTAGES

Incorporates all the advantages of copper

(Per meter) lower than the total price of copper

Less than the weight per meter

Products with the desired properties can be produced.

HVAC systems in a balanced combination of materials and components

 

MATERIALS

(At least 99.9% copper content) High Purity Copper

(With an aluminum content of at least 99.7%) of aluminum and aluminum alloy

 

Dimensions

 

Installation pipes

OEM Applications

Outside Diameter

1/4 ", 3/8", 1/2 "5/8 και"

6mm - 20mm

Thickness

0,80-1,20 mm

0,30-1,50 mm

 

 

SINGLE SIZE B1 OTTOCOOL
PIPE DIAMETER mm
1/4''
3/8''
1/2''
5/8''
PIPE THICKNESS mm
0,8
0,8
1
1,2
INSULATION THICKNESS mm
10
10
10
10
OPERATING PRESSURE bar
55
55
55
55
COIL LENGTH meters
25/50
25/50
25/50
25/50
COIL DIAMETER mm
800
800
850
850
TOTAL TRACK CONTENT meters
700/1000
600/1000
500/1000
500/800

 

DOUBLE SIZE B1 OTTOCOOL
PIPE DIAMETER mm
1/4 + 3/8
1/4 + 1/2
1/4 + 5/8
3/8 + 1/2
3/8 + 5/8
PIPE THICKNESS mm
0,8 + 0,8
0,8 + 1,0
0,8 + 1,2
0,8 + 1,0
0,8 + 1,2
INSULATION THICKNESS mm
10 + 10
10 + 10
10 + 10
10 + 10
10 + 10
OPERATING PRESSURE bar
55 - 55
55 - 55
55 - 55
55 - 55
55 - 55
COIL LENGTH meters
25
25
25
25
25
COIL DIAMETER mm
800
800
850
850
950
TOTAL TRACK CONTENT meters
500
500
400
400
400