Rubber Insulation :

In cooling, air-conditioning and industrial systems, the rubber insulation method provides the best performance through high quality raw material. Please find below the details regarding the technical specifications of the product.

 

Technical Features
Unit
ODE R-Flex ST
Heat Conductivity
W/mK
0.034 (-20ºC)
Coefficient (λ) DIN 52613
0.036 (0ºC)
and 52612
0.038 (+20ºC)
Water Vapour Diffusion
-
≥ 7.000
Resistance Coefficient (µ)
Fire Classification
-
Class O
BS 476 Part 6 1989
Corrosion Risk
DIN 1988/7 qualified
Heat Endurance
-200 / + 116 (Pipe)
-200 / + 85 (Plate)



• ideal solution in cooling, air-conditioning and industrial systems
• The warranty of the statement values through production in the most modern plants in the world
• The best performance through high quality raw material selection 
• Low coefficient of thermal conductivity (0,034 W/mK) maximum savings 
• Minimum condensation through high water diffusion resistance 
• Maximum security during fire through BS 476 Class 0 and DIN 4102 B1 Certificates 
• Toxicity and smoke test reports regarding that it does not emit toxic gas during fire 
• Test reports regarding that it is usable in food industry, submarines and subways 
• Minimum corrosion risk thanks to it neutral structure in accordance with DIN 1988/7 standard 
• Environment-friendly which does not contain HCFC - CFC 

 

Pipe Properties :
Cu-DHP annealed copper pipe (n. C12200) en 12735-1
Phosphorus deoxidised.
Chemical composition

Cu+Ag 99,9 % 0,015 % < P < 0,040 % with perfectly
Sealed ends and inwardly dehumified.
Dimensions and mechanical characteristics conforming to
ASTM B-280 or EN 12735-1.
Linear thermal expansion coefficient (for temperatures from
25 to 100 °ºC: 0,0000168 k.
Heat conduction at 20ºC = 364 w/m ºK
Unit breaking load: min. R = 220 n/mm2 (21 kg/mm²).
Elongation percentage: A% min = 45%.
Internal surface: Glossy and perfectly clean,
Conforming to astm b-280 legislation.
Phisical condition: Annealed.

 


DIMENSIONS
PIPE DIAMETER mm
1/4
3/8
1/2
5/8
3/4
7/8
PIPE THICKNESS mm
0,8
0,8
0,9
1
1
1,2
INSULATION THICKNESS mm
6/9/13
6/9/13
6/9/13
6/9/13
6/9/13
6/9/13
OPERATING PRESSURE bar
134
95
84
70
58
52
COIL LENGTH meters
50
50
50
50
50
25
COIL DIAMETER mm
800
800
850
850
950
950
TOTAL TRACK CONTENT m
700
700
600
600
500
400



  Copyright © 2009 - 2014 | Anadolu Copper Alloys Main Page | About Us | Products | References | Certificates | E-Catalog | Fairs | Contact